nautilus

SCADA, built like software. A Go + SvelteKit toolkit for building industrial control and supervisory systems the way software engineers already work, with version control, tests, CI/CD, and code review, instead of inside a proprietary vendor IDE.

Write your control logic in IEC 61131-3 (Structured Text, Ladder, Function Block, or Sequential Function Chart, the portable standard languages) or in native Go. Host it on a deterministic scan loop. Build the operator screens on the included SvelteKit component kit. Bring your own field I/O, redundancy and historian through small, documented interfaces. Develop it in VS Code. Ship it like any other binary.

For teams that want the libraries and the seams, not a walled garden.

Why

A PLC program should be code: diffable, reviewable, unit-tested, built by CI, rolled back with one command, and observable from your editor. Vendor tooling makes almost none of that possible. nautilus makes control logic a first-class software artifact and keeps the runtime a tiny, pure-stdlib core you can read.

Architecture

runtime/     scan loop · tag bus · program host (compile, hot-swap, retained state)
lang/st      IEC 61131-3 Structured Text: lexer, parser, lowering
lang/fbd     Function Block Diagram: netlist text ⇄ diagram model, transpiles to ST
lang/ld      Ladder Diagram: rung text ⇄ ladder model, transpiles to FBD
lang/sfc     Sequential Function Chart: steps, transitions, actions, transpiles to ST
lang/ir      typed IR + tree-walking virtual machine (pure stdlib)
io/          Driver seam — bring your own bus (Modbus, EtherNet/IP, OPC-UA, sim)
eip/         EtherNet/IP driver for Allen-Bradley Logix: pure-Go CIP stack,
             tag browse + UDT import codegen, polling io.Driver, Logix emulator
sparkplug/   Sparkplug B edge node (and host application) over MQTT
retain/      retained-memory stores: file, Kubernetes ConfigMap
leader/      redundancy: Kubernetes Lease leader election
oplog/       redundancy: a replicated log of operator intent (acks, shelves), agreed by a majority
hist/        historian seam + Postgres sink, `naut historian`
alarm/       ISA-18.2 alarms: rules over UDT members, ack/shelve, journal
acceptance/  virtual-time acceptance tests (`naut test`, `*_test.yaml`)
server/      tag API over HTTP: JSON snapshot, SSE stream, tag writes, alarms, program history
cmd/naut the developer CLI: new · run · test · check · build · pull · lsp · eip · sparkplug · historian · alarms
hmi/         SvelteKit digital-twin component kit + realtime SSE client
tools/vscode-iec/   VS Code extension: syntax, diagnostics, go-to-def, live values, diagram editors
tools/jitter/       scan-loop lateness harness: the numbers behind docs/design/realtime.md
rt/          harder real-time spikes beside the Go build (a Rust fast loop + shared-memory tag exchange)
examples/    four real plant projects — lift-station, batch-skid, remote-fleet, go-sdk — see examples/README.md

The public API is the seams. You implement interfaces to bring your world:

Interface You provide
io.Driver your field bus (Modbus / EtherNet-IP / OPC-UA / REST rack / sim)
retain.Store where retained memory persists — file and k8s ConfigMap ship in retain/
runtime.Coordinator redundancy / leader election — a k8s Lease elector ships in leader/
hist.Sink where process history is archived — Postgres + naut historian ship in hist/
alarm.Journal / alarm.Notifier where alarm events land — a ring, rotated JSONL, and Postgres ship in alarm/

Getting started

Platforms: nautilus is one static binary with no runtime dependencies. Every release ships builds for macOS (Apple Silicon and Intel), Linux (x86-64 and arm64), and Windows (x86-64 and arm64); the controller it builds runs anywhere the same binary does, from a laptop to a Raspberry Pi to a Kubernetes pod. VS Code is the editor experience on all three. The release page has the archives and a checksums.txt.

1. Install the CLI

macOS — pick arm64 for Apple Silicon, amd64 for Intel:

v=$(curl -fsSL https://api.github.com/repos/joyautomation/nautilus/releases/latest | grep -m1 '"tag_name"' | cut -d'"' -f4)
curl -fsSL "https://github.com/joyautomation/nautilus/releases/download/$v/nautilus_${v#v}_darwin_arm64.tar.gz" | tar xz naut
sudo mv naut /usr/local/bin/

Downloading with curl skips Gatekeeper's quarantine. If you fetched the archive in a browser instead and macOS refuses to open the binary, clear the flag once: xattr -d com.apple.quarantine /usr/local/bin/naut.

Linux — amd64 or arm64:

v=$(curl -fsSL https://api.github.com/repos/joyautomation/nautilus/releases/latest | grep -m1 '"tag_name"' | cut -d'"' -f4)
curl -fsSL "https://github.com/joyautomation/nautilus/releases/download/$v/nautilus_${v#v}_linux_amd64.tar.gz" | tar xz naut
sudo install naut /usr/local/bin/naut

Check it:

naut version

The command is naut, not nautilus. GNOME's file manager already owns /usr/bin/nautilus on essentially every Linux desktop, and sharing the name broke both ways: install ours on PATH and clicking Files in the dock launched the CLI (org.gnome.Nautilus.desktop runs Exec=nautilus by bare name); leave it off PATH and typing nautilus opened the file manager, which read the argument as a folder and showed "Unable to find … Please check the spelling and try again."

If you installed an earlier build as nautilus, remove it: sudo rm -f /usr/local/bin/nautilus. The project is still called nautilus — only the command changed.

Windows — PowerShell, amd64 or arm64:

$v = (Invoke-RestMethod https://api.github.com/repos/joyautomation/nautilus/releases/latest).tag_name
Invoke-WebRequest "https://github.com/joyautomation/nautilus/releases/download/$v/nautilus_$($v.TrimStart('v'))_windows_amd64.zip" -OutFile nautilus.zip
Expand-Archive nautilus.zip -DestinationPath "$env:LOCALAPPDATA\nautilus" -Force
[Environment]::SetEnvironmentVariable("Path", "$env:LOCALAPPDATA\nautilus;" + [Environment]::GetEnvironmentVariable("Path", "User"), "User")

Open a new terminal afterwards so the Path change is picked up.

Any OS, with Go 1.24+ installed:

go install github.com/joyautomation/nautilus/cmd/naut@latest

This puts the binary in $(go env GOPATH)/bin, which needs to be on your PATH. Whichever route you took, naut version should now answer.

The one binary is the whole toolchain: naut new (scaffold a project), run, test, check (the CI gate: compiles every program and cross-checks it against the manifest), build, pull (bring a controller's running program back into the repo), lsp (the language server the VS Code extension uses), and the eip, modbus, sparkplug, and historian tools.

2. Scaffold a project

naut new my-plant                      # the tour: 3 tasks, 3 IEC languages, simulated plant
naut new my-plant --template minimal   # one task, one program, one test
naut new my-plant --template sdk       # Go project, for a custom field bus
naut new my-plant --template sdk-demo  # Go project with plant physics in Go

A nautilus project is your logic and a manifest. Run, test, and ship it with the CLI alone — no toolchain:

cd my-plant
naut run        # scan loop + dashboard + tag API on http://localhost:8080
naut test       # acceptance tests, in virtual time
naut build      # emit ./my-plant — a self-contained controller binary

nautilus.yaml declares the tasks (one program file each, any language, own scan rates), the tags by role, the server, and the field driver (loopback for bring-up, EtherNet/IP by configuration). naut build appends the project to the runner and emits one deployable binary — no Go toolchain anywhere.

Your logic gets real tests. *_test.yaml files run against a virtual clock, so a ten-second on-delay or a PI loop's settling time is asserted exactly, deterministically, in milliseconds — the assertions a wall clock makes impossible:

  - name: low-temp alarm waits its full 10 s
    suspend: [sim]                    # freeze the plant; drive the value directly
    given: { TempC: 45.0 }
    steps:
      - advance: 9.5s
        expect: { TempLowAlm: false } # the TON has not elapsed
      - advance: 1s
        expect: { TempLowAlm: true }  # ... and now it has

The fixture is nautilus.yaml itself — tasks, rates, roles, seeds — so a retuned gain can't drift away from what the tests verify. Assertions are tag matchers or ST expressions (ABS(TempC - TempSP) < 0.5) compiled by the same compiler as your logic.

Go is the SDK, not the base: --template sdk when you need a custom field bus or richer simulation physics. Same runtime, with the manifest written as code.

Run it bare for the interactive form, sv-create style — pick the template, the program language, and the features (CI workflow, VS Code setup, git init). An sdk template also asks for a module path, and gives you main.go, program.st, a driver.go seam to fill in, Go acceptance tests, CI, and .vscode/ recommendations.

3. Run and test it

cd my-plant
naut test    # the acceptance suite, in virtual time
naut run     # scan loop + tag API on http://localhost:8080

An sdk project is an ordinary Go program — go mod tidy, go run ., go test ./... — and its Go tests get the same virtual clock through the acceptance package.

Open http://localhost:8080 for the built-in live dashboard, or GET /api/state for the raw tag snapshot. Setpoints are click-to-set right in the tag table (BOOLs get a toggle); inputs and outputs are not editable, because the driver rewrites one before every scan and the logic rewrites the other after. Reads are open; set NAUTILUS_TOKEN=<secret> to require a token on writes.

4. Develop in VS Code

Install nautilus IEC 61131-3 from the VS Code Marketplace or Open VSX (code --install-extension joyauto.vscode-iec; Switch to Pre-Release Version on the extension page follows main). Open your project folder — it recommends the extension — and with go run . running you get compile diagnostics as you type, go-to-definition / hover / completion, and live tag values as pills next to identifiers in program.st.

On macOS, VS Code launched from the Dock or Spotlight gets the login PATH, not your shell's, so it may not find naut even though your terminal does. If the extension reports it could not start the language server, run nautilus: Install or Update the naut CLI, set nautilus.cliPath to the full path (which naut), or launch VS Code from a terminal with code ..

5. Make it yours

  • Write control logic in program.st, or in .ld, .fbd, or .sfc; the graphical languages open in full diagram editors in VS Code.
  • Swap plant.go for a real io.Driver — Modbus, EtherNet/IP, OPC-UA, your bus — when you have hardware. The control logic doesn't change.
  • Add an HMI: npm install @joyautomation/nautilus-hmi in a SvelteKit app for SCADA faceplates and an SSE realtime client. Build it with adapter-static and a manifest project can serve the build itself — server: { hmi: ./hmi/build } — so one binary is the whole deploy; see the tag-model guide's "Serving the HMI from the controller".
  • Ship it as one binary: naut build for a manifest project, go build for an SDK project. The scaffolded CI gates on naut check, naut test, and naut build; naut new --deploy adds a Dockerfile, a redundant-pair Kubernetes manifest, and the workflow that ships a merged commit to the controller.

Under the scaffold, a complete controller — an IEC program on a 10 Hz scan loop driving a field device — is about 30 lines:

rt, _ := runtime.New(runtime.Options{
    Program: program,             // IEC 61131-3 Structured Text (go:embed)
    Driver:  NewPlant(),          // anything implementing io.Driver
    Scan:    100 * time.Millisecond,
    DtTag:   "ScanDtS",
    Tags: []runtime.TagDef{      // each tag's role, seed, and HMI docs — once
        runtime.Input("LevelPct", runtime.Unit("%")),
        runtime.Input("TempC", runtime.Unit("°C")),
        runtime.Setpoint("TempSP", 65.0, runtime.Unit("°C")),
        runtime.Setpoint("Kp", 12.0),
        runtime.Setpoint("Ki", 0.15),
        runtime.Output("PumpRun", runtime.Init(false)), // logic reads it back
        runtime.Output("Heater", runtime.Unit("%")),
    },
})
go rt.Run(ctx)                    // read inputs → run program → write outputs, every scan

How tags work — where they come from, which role fits which job, and the one rule that bites (reads fault, writes create) — is spelled out in The tag model below.

Or, from a clone of this repo, run the worked example:

go run ./examples/go-sdk
nautilus · go-sdk (heated tank) — tag API on http://localhost:8080 — Ctrl+C to stop
level  60.0%  temp  60.0°C  pump off  heater  61%  scans 9
level  59.9%  temp  60.0°C  pump off  heater  62%  scans 19
level  59.9%  temp  60.0°C  pump off  heater  62%  scans 29

The control logic itself lives in examples/go-sdk/program.st — pump hysteresis and a PI temperature loop, in plain Structured Text. The plant physics (plant.go) shows the shape a real field-bus driver takes — see examples/go-sdk/README.md for the whole SDK story. Everywhere else in examples/ the plant is a manifest project — no Go — starting with examples/lift-station.

Talking to a real PLC (EtherNet/IP)

Point the importer at an Allen-Bradley Logix controller and it generates the types and bindings your project needs — committed source, not runtime config:

naut eip browse --host 192.168.1.10                 # see what's on the controller
naut eip import --host 192.168.1.10 \
  --tags 'Line1*,Program:MainProgram.*' \
  --writable 'Line1Cmd*'

That writes eip_types.st (a TYPE block mirroring the controller's UDTs plus suggested VAR_EXTERNAL declarations) and eip_manifest.go (the tag manifest). Wire it into main.go:

driver, err := eip.New("192.168.1.10", EIPManifest,
    eip.WithSlot(0),
    // Polling policy is configuration, not codegen: re-running the import
    // refreshes the tag catalog without touching these.
    eip.WithScanRate(500*time.Millisecond),           // default scan class
    eip.WithScanClass("fast", 100*time.Millisecond),
    eip.WithScanClass("slow", 10*time.Second),
    eip.WithTagClass("fast", "Line1_PIT_*"),          // globs on tag/device names
    eip.WithTagClass("slow", "*_Totals"),
    eip.WithTagClass(eip.NoPoll, "Line1Cmd*"),        // cataloged + writable, never polled
)
driver.Start(ctx)
rt, err := runtime.New(runtime.Options{
    Program: program,
    Driver:  driver,
    Inputs:  driver.InputNames(),
    Outputs: driver.OutputNames(),
})

The driver polls each scan class on its own interval over one connection (UDTs arrive as real struct values in ST), validates the manifest against the live controller at startup so type drift fails loudly, and writes changed outputs back on change — the runtime behaves like a PLC peer on the network. Pure Go, no cgo; tested against an in-repo ControlLogix emulator (eip/logixserver).

No PLC on the bench? naut logix emulate --l5x UpstreamLine.L5X serves a Logix Designer export's tags — UDTs, program tags, initial values — as a ControlLogix on 127.0.0.1:44818 (--ramp makes the numbers move), so browse, import and a driver: {type: eip} project all run against it.

Writing Logix programs in nautilus (experimental)

The other direction: write the logic in nautilus — ladder or ST, in git, tested on the nautilus runtime — and deploy it to a ControlLogix or CompactLogix, with Studio 5000 running headless behind a logixd agent as compiler and loader. Add a target: logix section to nautilus.yaml and:

naut check                   # also enforces the Logix subset, by rule ID
naut logix deploy --online   # write the L5X, build it, online-edit the controller
naut test --target logix     # the same acceptance tests, on the controller

naut logix import --project <dir> Line.L5X turns an existing export into such a project. This is a proof of concept, verified on one controller family at one firmware revision; see the Authoring for Logix guide and docs/design/logix-authoring.md.

Talking to Modbus TCP devices

Field devices that aren't a Logix PLC — PID loops behind a gateway, VFDs, analysers, power meters — come from a committed device map: register maps off the datasheet once per device type, hosts and unit-ids once per instance.

naut modbus import --map devices.yaml --plan

That writes modbus_manifest.yaml and tags/modbus.yaml — both generated, never hand-edited, byte-identical on re-run — and --plan prints the block-read plan: a four-channel analyser's floats coalesce into one FC3 request instead of four. In a manifest project the driver is configuration:

driver:
  type: modbus
  manifest: modbus_manifest.yaml   # from `naut modbus import`
  scan-rate: 1s
  scan-classes: { fast: 500ms, slow: 2.5s }
tag-files: [tags/modbus.yaml]

Addresses are 0-based PDU addresses (40001 is holding 0); word and byte order are per source, because the same hardware ships both ways. A Modbus exception marks just that block bad and keeps polling; a transport failure reconnects with backoff while values hold and <source>__Online goes false. naut modbus serve stands in for the whole plant on one listener, so the bench needs no hardware. examples/lift-station runs a whole plant against it (devices.yaml, modbus_manifest.yaml), and the Modbus TCP guide covers the rest.

More than one bus: drivers:

A controller that polls a Modbus skid and consumes a Sparkplug fleet on the same scan lists both. drivers: is the plural of driver: — each entry is the same shape, with an optional name that status rows and error messages use (default: the type, deduped as eip-2 when a type repeats):

drivers:
  - type: modbus
    manifest: modbus_manifest.yaml
  - type: sparkplug-host
    name: fleet
    broker: "tcp://mqtt.plant:1883"
    group-id: Plant
    host-id: plant-scada
    manifest: sparkplug_manifest.yaml

Reads fan out and merge, writes route to the driver whose bindings claim the tag, and ownership is disjoint by construction: a tag delivered by two drivers is a load error naming both, the same no-last-wins rule tag files keep. /api/drivers shows one row per driver, and on a sparkplug: edge node each field connection is its own device, born and killed by its own link. The memory loopback cannot join a list — it owns whatever is written to it, which is exactly what makes it unroutable next to another driver.

IT hardware as tags (SNMP, Redfish, node_exporter)

A switch port is a UDT, a failed PSU is an ISA-18.2 alarm, and a rack publishes Sparkplug B like any plant asset: three drivers deliver one shared UDT set — Server, Fan, PSU, TempSensor, Switch, SwitchPort, PDU, PDUOutlet, UPS — so the 3D view, alarms, history and Sparkplug work on a server rack with no special cases.

naut snmp import --tag SW1 --host 192.168.1.2 --version 3 --user mon --auth sha256 --priv aes128
naut redfish import --tag NODE1 --host https://bmc1 --user mon --password-env BMC_NODE1_PASSWORD --insecure
naut prometheus import --tag HOST1 --url http://host1:9100/metrics

Each writes <proto>_manifest.yaml + tags/<proto>.yaml (generated, byte- identical on re-run) and the same hw_types.st; browse --record captures a device so the import, the bench stand-in (naut <proto> serve) and the tests all run from the recording. Credentials are never in a file: the manifest names the variable (SNMP_SW1_COMMUNITY, SNMP_SW1_AUTH, BMC_NODE1_PASSWORD) the driver reads where it runs, and naut check warns when it is unset. Intervals are seconds, not scan rates:

drivers:
  - type: snmp
    manifest: snmp_manifest.yaml
    scan-rate: 5s
    scan-classes: { slow: 60s }
    tag-classes: { slow: ["*.Name", "*.Alias", "*.Serial"] }
  - type: prometheus
    manifest: prometheus_manifest.yaml
    scan-rate: 15s
alarms:
  site-from: "^([A-Za-z0-9]+?)(?:_|$)"
  rules:
    - { match: { type: SwitchPort, member: Down }, priority: medium, on-delay: 15s, enable: "{site}__Online" }
    - { match: { type: Fan, member: Fault }, priority: high, on-delay: 30s, enable: "{site}__Online" }

Counters become rates (InBps, ErrorRate) with 32-bit wrap and 64-bit reset handled; a device that stops answering keeps its last values (Stale) with <id>__Online false; a refused OID or 404 resource marks just that tag Bad. Writes are off unless a person adds one: a PDU outlet or a server power command is its own scalar output tag, leader-only, confirmed, never generated. examples/it-rack runs a switch and a host against the stand-ins and against real devices with the same tags; the IT hardware guide covers the rest. Each driver is tested in CI against a foreign stack: snmpsim, DMTF's Redfish mockup server, a real node_exporter release.

Online edits — change logic while it runs

nautilus has two planes. The cold plane — connections, the tag manifest, scan classes, server wiring — is Go, and changes ship through CI/CD as a new binary. The hot plane — the ST program and tag values — can change live, the way you online-edit a traditional PLC. Because the program is data on a VM, a warm swap carries retained state (PID integrals, timers, counters) across by name and type; a failed compile leaves the running program untouched, so a typo can never fault the controller.

Enable it per controller (off by default — pushing logic is code execution on a control system):

srv := server.New(rt, server.Options{OnlineEdits: true})

Then from VS Code: Download Program to Controller warm-swaps your open program, Diff Program with Controller shows running-vs-workspace, and a status-bar indicator flags when the controller runs something other than the committed file. Edits are ephemeral by design — a restart reverts to the program the binary embeds, so committing the ST to git is the only way an edit becomes permanent. The rule of thumb falls out of the two planes: logic you want to tune online, write in ST; infrastructure, write in Go.

Pulling a field edit back to git closes the loop. Pull Program from Controller (VS Code) or naut pull --host <controller> writes the running program back into your program file — the inverse of download — so you review it with git diff and commit. Only the program file is rewritten; generated type files are never touched. naut pull --check reports drift and exits non-zero, so CI can fail a build when a controller has un-pulled edits. Composition is a single definition shared by the runtime, the language server, download, and pull, so a program round-trips losslessly.

Working against a remote controller. All of this — live values, online edits, pull — works over the network, not just against a local process. A scaffolded controller binds loopback by default; set NAUTILUS_ADDR=0.0.0.0:8080 to expose the tag API to other machines, and point the editor at it with the nautilus.runtimeUrl setting (naut pull takes --host). Exposing the API on the network also exposes its write surface, so set NAUTILUS_TOKEN on the controller and the matching nautilus.token in the editor — reads and naut pull stay open, but tag writes and online edits then require the token.

Forcing. A tag can be held at a value against the field and the logic — the PLC force table — from the editor (Force…, an F on every forced value, N forces active in the status bar) or POST /api/forces. A running SFC chart can be jumped to a step or have one transition fired. Forces are not retained across a restart and a redundancy takeover drops them; see the forcing guide.

Alarms

An alarm engine is a small thing when alarms are just tags. Your logic already computes the bits — a limit comparison, a fault contact, a .HH member an edge node published. alarms: in the manifest adds the part a person needs: an ISA-18.2 active list, acknowledge, a shelf that always expires, and an append-only journal, served at /api/alarms* with a counts-only summary on every stream frame. rules: generate definitions in bulk by matching a UDT type and a member, so a dozen rules cover a fleet's thousands of alarms and naut alarms list prints what they became. Acknowledgement is host state — never written back to the edge, persisted through retain, so a restart or a failover cannot resurrect four hundred acked alarms as unacked. Acceptance tests get an alarms: key and ack:/shelve: verbs, and the engine reads the runtime's clock, so a five-minute on-delay is asserted exactly in virtual time. See examples/lift-station (and examples/remote-fleet's rule expanded across a shared Template) and the Alarms guide.

Publishing to MQTT (Sparkplug B)

Expose a controller's tags to a Sparkplug host (Ignition, any Sparkplug-aware SCADA) with the sparkplug package. The runtime is the edge node; each field connection becomes a device whose birth/death follows its link, and the node is read-only unless told which tags a host may write:

node, _ := sparkplug.New(rt, sparkplug.Config{
    BrokerURL: "tcp://broker:1883", GroupID: "Plant", EdgeNode: "Line1",
    BdSeqFile: "/var/lib/nautilus/line1.bdseq",
},
    // Publish classes are report-by-exception groups, like scan classes:
    sparkplug.WithDefaultRBE(sparkplug.RBE{Deadband: 0.5, MaxInterval: 30 * time.Second}),
    sparkplug.WithPublishClass("fast", sparkplug.RBE{Deadband: 0.1, MaxInterval: 5 * time.Second}),
    sparkplug.WithMetricClass("fast", "PIT_*"),
    // NCMD/DCMD writes reach only these; every other write is refused.
    sparkplug.WithWritable("LevelSP", "Pump*.SpeedSP"),
    // The EtherNet/IP driver's tags become a device; DBIRTH/DDEATH track its health.
    sparkplug.WithDevice(sparkplug.Device{
        ID: "plc1", Tags: driver.InputNames(),
        Health: func() bool { return driver.Health().Connected },
    }),
)
node.Start(ctx)

Types map faithfully (BOOL→Boolean, integer→Int64, REAL→Double, UDT→Template), a SCADA host can write the writable tags back via NCMD/DCMD, and Node Control/Rebirth is honored. The node passes the Sparkplug TCK edge-node profile — CI runs the joyautomation/sparkplug-tck-go harness against a live node on every push. MQTT and protobuf live only in this package; the runtime core's one dependency outside the Go standard library is gopkg.in/yaml.v3.

Consuming Sparkplug B (host)

The other side of the wire: driver: {type: sparkplug-host} makes a project a Sparkplug B host application, consuming a whole group of edge nodes as role: input tags instead of publishing its own:

driver:
  type: sparkplug-host
  broker: "tcp://mqtt.plant:1883"
  group-id: Plant
  host-id: plant-scada          # STATE topic spBv1.0/STATE/plant-scada
  manifest: sparkplug_manifest.yaml   # from `naut sparkplug import`
tag-files: [tags/sparkplug.yaml]

naut sparkplug import --broker ... --group ... (live) or --sites sites.yaml (offline, no broker — CI-buildable) generates the manifest, tag file, and Template types. Reads fault until a site's first birth, so guard logic on the driver-synthesized <site>__Online companion; writes leave as NCMD/DCMD, and a write to a site that is offline is queued per node and delivered on its next birth, unless the birth already reports that value. A UDT is never written as a whole — bind its controls per member (member: Speed, or --writable 'Motor1.START,*.HSP') and each write goes out as a partial template the edge merges, leaving the members the site is driving untouched. Both the edge-node and host-application TCK profiles pass in CI. See examples/remote-fleet (three edge sites and a scada host) and the host guide.

Four languages, one program model

A program file is .st, .fbd, .ld, or .sfc: pick per task, mix freely in one controller. The graphical languages are text first: an .fbd is a netlist, an .ld is rung text, an .sfc is a step/transition list, all of them diff/review/merge like code, and the VS Code extension projects them into a full graphical editor (right-click → "Open With → FBD Diagram" / "Ladder Diagram" / "SFC Diagram") where every gesture is a structural edit to the text underneath.

(* interlocks.ld *)
PROGRAM Interlocks
VAR_EXTERNAL
    TempC : REAL; HiTempAlm : BOOL; HornAck : BOOL; Horn : BOOL;
END_VAR
LD
  RUNG hitemp (* comparison as a contact, with a 5 s on-delay *)
    GT(TempC, 90.0) t2:TON(PT := T#5S) ( HiTempAlm )

  RUNG horn (* the alarm sounds the horn until the operator acks *)
    HiTempAlm /HornAck ( Horn )
END_LD
END_PROGRAM

Rung grammar: series = AND, [ a | b ] = OR (nests), /x = NC contact, ( x ) / ( S x ) / ( R x ) coils, FN(args) as a contact (must yield BOOL), inst:TYPE(args) puts a timer/counter in the rung with power driving its standard pin, and ET => Var captures block outputs. Each language transpiles one hop (ld → fbd → st) into the same IR, so functions, user FUNCTION_BLOCKs, arrays, diagnostics, live values, online edits, and visual diffs work identically everywhere. naut new --language ld (or fbd) scaffolds a project in that language. The full reference — evaluation semantics and every built-in — is docs/functions.md.

The tag model

The tag store is the seam everything meets at: the IEC program, the field driver, the HMI/API, and the editor's live values all read and write the same named values. One scan looks like this:

driver.ReadInputs() ──(Input tags)──▶ ┌───────────┐ ──(Output tags)──▶ driver.WriteOutputs()
                                      │ tag store │
HMI / POST /api/tags ──(writes)─────▶ │           │ ──(reads)────────▶ HMI / editor pills
                                      └───────────┘
                                        ▲       │
                                 program writes │ program reads
                                     (coils)    ▼

A VAR_EXTERNAL declaration binds a name; it does not create the tag. Declaring TempC : REAL; in your program means "resolve this name in the tag store at scan time", and nothing more. Existence comes from a write, and there are exactly four writers:

  1. a seed in the Go composition (initial value, exists from scan one),
  2. a driver delivering it as an input each scan,
  3. an operator writing a tag the project declares through the HMI or POST /api/tags (a whole tag, or one member of a UDT tag — see below; a name nothing declares, a CONSTANT's included, is refused with a 400 naming it, never created),
  4. the program itself assigning it (a coil write creates the tag).

The one rule that bites: writes create, reads fault. Reading a tag nobody has ever written stops the scan with undefined tag <name> — deliberately, so a mis-wired binding fails loudly instead of running on a silent zero. The classic trap is a seal-in latch that reads its own coil on scan one, before the first write; the fix is a seed. (In the FBD diagram, with live values on, externals with no backing tag are flagged — an amber no tag badge in the vars panel and on any chip that reads one — so you see this before the download, not after.)

Declaring tags: one entry per tag

runtime.Options.Tags states each tag's role once — which direction it moves each scan, its initial value, and its HMI documentation — instead of spreading the name across the flat Inputs/Outputs/Seed/Meta fields (all of which still work and compose with Tags):

Tags: []runtime.TagDef{
    // Field input: the driver produces it. NOT seeded — if the driver
    // doesn't deliver it, you want the loud fault, not a silent zero.
    // (The name must also appear in the driver's ReadInputs map.)
    runtime.Input("TempC", runtime.Desc("Tank temperature"), runtime.Unit("°C")),

    // Operator setpoint / config: seeded so it exists from scan one;
    // the HMI or POST /api/tags writes it later.
    runtime.Setpoint("TempSP", 65.0, runtime.Unit("°C")),

    // Field output: the logic produces it, the driver consumes it.
    // Init() any output the logic also READS — the seal-in latch.
    runtime.Output("PumpRun", runtime.Init(false), runtime.Desc("Pump run command")),

    // Logic-owned state that must survive read-before-write: latches,
    // integrators, mode words.
    runtime.State("Mode", int64(0), runtime.Desc("0=off 1=auto 2=manual")),
},

Picking a role, by use case:

You want a tag that… Use Backed by
comes from a sensor / the field Input(name, …) driver ReadInputs map + this entry
goes to an actuator / the field Output(name, …) your logic writes it (coil)
…and your logic also reads it (latch) Output(name, Init(v), …) the seed covers scan one, then the coil
an operator adjusts (setpoint, gain, limit) Setpoint(name, initial, …) the seed, then HMI / POST /api/tags
your logic owns across scans (integrator) State(name, initial, …) the seed, then the coil
the HMI watches but the field never sees plain coil write — no entry the program creates it on first write

Adding a new field input end to end is three lines in three places, all by the same name: declare it in the program (VAR_EXTERNAL testExt : REAL; — or from the diagram's vars panel), produce it in the driver ("testExt": p.testExt in the ReadInputs map), and bind it in the composition (runtime.Input("testExt")). The Inputs list is a deliberate allowlist — a driver can't spray arbitrary names into the store — which is why the middle step alone isn't enough.

Writing a member: POST /api/tags with Tag.Member

A UDT tag is one value in the store, so an operator writing one of its members is a read-modify-write of the whole struct. POST /api/tags does that for you — name takes a dotted member path, to any depth:

curl -X POST localhost:8080/api/tags -d '{"name": "P101.START", "value": true}'
curl -X POST localhost:8080/api/tags -d '{"name": "P101.LVL.HSP", "value": 60}'

value may also be an object, to set several members of one tag at once: {"name": "P101", "value": {"START": true, "LVL": {"HSP": 60}}}. That is a merge — members the object doesn't name keep their current values. (Deliberately unlike init: seeding, which zero-fills what its mapping omits: seeding builds a value from nothing, a write edits one the plant is already running on.)

The rules:

  • Nothing is created. An unknown tag, a misspelled member, or a member path into a scalar tag is a 400 with the reason — tag P101: unknown member STRAT (did you mean START?) — never a new top-level tag literally named P101.STRAT, which no program reads and a Sparkplug edge would publish as a bogus metric.
  • The leaf keeps its type. A number lands on a REAL member as a REAL and on a DINT member as an integer; a mismatch is tag P101.START: want BOOL, got a number rather than a silent retype.
  • The role rule is the root tag's. A member of a driver-owned Input is refused (the driver replaces the whole tag before the next scan, so the edit could not survive one cycle); setpoints, state and outputs are writable — an output being exactly how a Sparkplug host commands an edge node. A struct-typed Output needs an Init(...) to exist before the first write, like any tag the operator addresses.
  • GET /api/meta reports "memberWrites": true, so an HMI can tell a controller that resolves member paths from an older one that would have swallowed them.

The same paths work everywhere else a tag is addressed: a test manifest's given:/expect:, the dashboard's tag table (expand a writable struct and each leaf is editable), and the HMI kit's rt.writeTag('P101.START', true), which returns the controller's reason when it refuses.

Structuring logic: functions and function blocks

When a program outgrows one file, IEC 61131-3's unit of reuse is the FUNCTION_BLOCK (stateful — each instance keeps its own timers, integrals, latches) and the FUNCTION (stateless). nautilus sticks to the standard here on purpose: there is no vendor-style "call another program" — a program is a scheduling unit, a function block is a reuse unit, and reaching for reuse means writing a block.

Blocks live in library files — a .st file holding only TYPE, FUNCTION, and FUNCTION_BLOCK declarations, or a .ld / .fbd file with no PROGRAM — and compose ahead of the program:

//go:embed blocks.st
var blocks string

rt, _ := runtime.New(runtime.Options{
    Program:   program,            // .st or .fbd
    Libraries: []string{blocks},   // TYPEs, FUNCTIONs, FUNCTION_BLOCKs
    ...
})
(* blocks.st *)
FUNCTION_BLOCK PI
VAR_INPUT  SP : REAL; PV : REAL; KP : REAL; KI : REAL; DT : REAL; END_VAR
VAR_OUTPUT OUT : REAL; END_VAR
VAR integral : REAL; err : REAL; END_VAR
err := SP - PV;
integral := LIMIT(0.0, integral + KI * err * DT, 100.0);
OUT := LIMIT(0.0, KP * err + integral, 100.0);
END_FUNCTION_BLOCK
(* program.st — one instance per control loop *)
VAR tic : PI; END_VAR
tic(SP := TempSP, PV := TempC, KP := Kp, KI := Ki, DT := ScanDtS);
Heater := tic.OUT;

The pieces that make this first-class rather than a convention:

  • Callable from any IEC language, and writable in any. The same PI block instantiates from an FBD diagram (tic : PI(SP := TempSP, ...)) exactly like a built-in TON. Blocks are also AUTHORED in any language: a .ld file with no PROGRAM is a library of ladder subroutines — FUNCTION_BLOCKs whose bodies are rungs, with pins and per-instance retained state, which is what IEC gives you instead of a JSR. See docs/functions.md and examples/lift-station's lib/motor.ld, a MotorStarter block instantiated once per pump.
  • The tooling composes the same way. The VS Code extension, the LSP, naut check, and naut pull all treat the project's library files (PROGRAM-less files in the root and anywhere under lib/) as in-scope for the program, byte-identically to Libraries — so online edits round-trip losslessly and CI sees what the runtime sees.
  • Instance state is retained. A block's VAR section persists across scans, and PLC-style online edits carry it across program swaps by name and type — a PI keeps its integral through a live logic change, like a real controller.
  • Pins are typed by your model, not just by scalars. A pin may be a user TYPE from the same library — VAR_INPUT IN : AnalogInput; — and VAR_IN_OUT AI : AnalogInput; binds the caller's variable (a local, a struct field, or a VAR_EXTERNAL UDT tag) so the block's writes land back in it. A block whose UDT already names its own inputs and outputs takes one pin instead of thirty. See docs/functions.md.

naut new scaffolds this shape: the PI controller ships in blocks.st, instantiated from program.st. (This one is worth writing by hand once to see how it works; for real loops reach for the built-in PID — anti-windup, bumpless auto/manual, derivative-on-PV filtering, diagnostics — see docs/functions.md.)

More than one program: tasks

The spec's answer to "many programs" isn't calling between them — it's the resource/task model: several programs scheduled at their own rates against one shared tag store. Options.Tasks is exactly that:

rt, _ := runtime.New(runtime.Options{
    Program: fastLogic,           // the MAIN task: owns field I/O
    Scan:    10 * time.Millisecond,
    Tasks: []runtime.Task{
        {Name: "temperature", Program: pidLoops, Scan: 250 * time.Millisecond, DtTag: "PidDtS"},
        {Name: "totals", Program: totalizers, Scan: time.Second, DtTag: "TotDtS"},
    },
})

Tasks run concurrently, and every scan still sees a consistent store: each scan copies its program's external tags in, executes privately, and commits what changed as one unit, so a fast task never waits behind a slow one and a reader never sees a scan half-done. Two tasks writing the same tag resolve by commit order (last wins), as on any PLC with shared globals — give a tag one owner. The main task reads inputs and writes outputs; additional tasks compute against the store at their own pace, each with its own measured-dt tag and its own health in Stats().Tasks (rendered in the built-in dashboard and the HMI kit's ScanDiagnostics).

A task can also be placed: cpu: 2 pins its thread to a core and priority: 50 runs it under SCHED_FIFO (Linux; needs CAP_SYS_NICE). A request the OS refuses is logged and shown on the task's row as REFUSED, and the task runs normally — never a silent fallback. Measured honestly: pinning alone on a stock kernel with nothing else changed makes a fast task worse, because it can no longer move off a busy core; pin only together with an isolated core (isolcpus=) or a real-time priority. The dashboard's lateness block (late, overruns, missed, p50/p99/p99.9/max per task) is how you know. See the scan timing guide and docs/design/realtime.md for the measurements.

Every program online-edits, both directions. Programs are addressed by POU name — PROGRAM <Name> is a program's identity. GET /api/program lists the resource's programs; a PUT routes automatically by the POU name in the submitted source, and ?pou= / ?task= select one explicitly for GET/rollback. In VS Code that means a workspace with one program file per task Just Works: open the file, Download/Diff/Rollback target that task's program, retained state carries across the swap. And naut pull reconciles the whole resource: every controller program pulls back into the workspace file declaring its POU (a new program lands in <POU>.st/.fbd), so a field edit to any task is reviewable and committable — --check fails CI on drift in any of them.

The full language reference — how a scan evaluates each language, ladder power-flow semantics, and every built-in operator, function, and function block with signatures and behavior — is in docs/functions.md.

Status

Pre-1.0, and the foundation Joy Automation builds SCADA systems on. Every artifact is versioned on its own: the CLI by v* tags, the VS Code extension on the Marketplace stable channel (pre-release tracks main for early fixes), the HMI kit on npm. What ships today:

  • ✅ lang/st + lang/ir — the Structured Text VM (pure stdlib, tested)
  • ✅ lang/stgen — build ST type declarations functionally in Go and render them to source (stgen.Struct("Motor", stgen.Field("Speed", stgen.REAL), …)), for generating UDTs from a schema; validates output by compiling it. This is the codegen path — the compiler stays the single source of truth
  • ✅ runtime — scan loop, tag bus, program host + hot-swap, and PLC-style online edits: warm-swap the ST program while it runs, carrying retained state (PID integrals, timers, counters) across by name and type, with one-step rollback
  • ✅ io — the Driver seam + an in-memory driver
  • ✅ alarm — ISA-18.2 alarms declared in the manifest: rules that expand over UDT members, on/off delays, acknowledge and time-boxed shelve (retained across restart and failover), suppression on a dark site, and a journal with ring / rotated-JSONL / Postgres sinks. Five /api/alarms* routes, a summary on the SSE frame, and alarms: matchers in the acceptance harness
  • ✅ sparkplug — MQTT Sparkplug B edge node: publishes the tag store to a broker (the runtime is the edge node; each io.Driver is a device whose DBIRTH/DDEATH tracks its connection health), faithful datatypes, UDTs as templates, NCMD writeback, and publish classes with report-by-exception (deadband + min/max interval), mirroring scan classes. Passes the joyautomation/sparkplug-tck-go edge-node conformance profile in CI
  • ✅ eip — EtherNet/IP driver for ControlLogix/CompactLogix: pure-Go (no cgo) CIP client with connected messaging and batched reads, tag-list + UDT template upload, naut eip import codegen (ST TYPE block + Go tag manifest), write-on-change outputs, and a Logix controller emulator (eip/logixserver, naut logix emulate) for hermetic integration tests and PLC-free demos
  • ✅ modbus — Modbus TCP driver: block-read planner (one request per device instead of one per variable), per-source word/byte order, scan classes, per-tag quality that tells a refused register (exception → that block bad, siblings good) from a dead link (reconnect backoff, values hold), keep-alive rewrite: outputs, naut modbus import|browse|serve|tags codegen and commissioning tools, and an in-process slave plus a pymodbus foreign-stack run in CI
  • ✅ snmp, redfish, prom on hw — IT hardware as tags: one UDT set (Server, Fan, PSU, TempSensor, Switch, SwitchPort, PDU, PDUOutlet, UPS) delivered by three drivers on a shared poll base (intervals, stale-after freshness, counter→rate, per-tag Bad, __Online companions), profiles for IF-MIB/ENTITY/UPS-MIB/CyberPower, legacy and current Redfish, and node_exporter; naut snmp|redfish|prometheus import|browse|serve|tags with recordings that make the bench and the tests hardware-free; foreign stacks in CI (snmpsim, DMTF Redfish-Mockup-Server, node_exporter)
  • ✅ server — tag API: JSON snapshot, SSE stream, tag writes (HMI + editor), a gated program API for online edits (GET/PUT /api/program, rollback), and (server.hmi) serving a built HMI at "/" with SPA fallback, so the controller can be the whole deploy — no separate web server
  • ✅ tools/vscode-iec/ online edits — Download Program to Controller, diff running-vs-workspace, rollback, and a sync-status indicator
  • ✅ cmd/naut — CLI: interactive project scaffold, headless ST compile check for CI, and the ST language server
  • ✅ tools/vscode-iec/ — VS Code extension: syntax, compile diagnostics, go-to-definition, hover, completion, inline live tag values
  • ✅ hmi/ — @joyautomation/nautilus-hmi on npm: Svelte 5 SCADA faceplates (Tank, Gauge, Trend, Pump, Valve…), app primitives, a generic SSE realtime client, and a themeable token layer
  • ✅ lang/sfc — Sequential Function Chart: steps, transitions, and actions on the same IR, with LSP support and a graphical VS Code editor
  • ✅ examples/ — four real plant projects covering every language and driver: lift-station (the flagship — SFC/FBD/LD/ST, Modbus, alarms, online edits, a custom-component HMI), batch-skid (SFC/FBD/LD, an EtherNet/IP line handshake, a read-only .L5X diffed between revisions), remote-fleet (three Sparkplug B edge sites and a Sparkplug host SCADA), and go-sdk (the one Go-tier example, for the SDK story) — see examples/README.md

Roadmap

  • An HMI starter in naut new
  • Native-Go function blocks alongside ST (both lowering to the same IR)
  • Vendor-format import (Studio 5000 L5X, TIA, PLCopen XML) → nautilus