Member

TA's interface spec (archived copy, input bit layout) encodes radiation as V110 TTTT TTTT TTTT, i.e. type bits 0x6000. pyblnet used 0x4000 (an undocumented type).

The value was decoded correctly anyway (radiation falls through to the default conversion), but direct-mode inputs got type: None and no unit_of_measurement instead of radiation / W/m². pyblnet-async also uses 0x6000.

The updated parser test fails on master.

TA's interface spec encodes radiation inputs as V110 TTTT TTTT TTTT,
type bits 0x6000, not 0x4000. The value was decoded correctly anyway
since radiation falls through to the default conversion, but the input
type was reported as None instead of radiation, so fetch() gave it no
unit. pyblnet-async uses 0x6000 as well.